03 · Current sensor selection

CT clamp installation: clamp the L wire only, arrow pointing toward the load

This chapter answers two questions:

  1. Which current sensor to choose for a given load.
  2. How to tell the rbAmp module about your choice so that the factory calibration for that combination loads automatically.

The physical wiring of the sensor (clamp orientation, L/N polarity check) is covered in 04_hardware.md. This chapter is about choosing the model and the API calls.


Sensor class

rbAmp modules work with CT clamps from the SCT-013 family. The sensor class is determined by the module's hardware revision and is set at the factory — the user reports their choice via dev.set_sensor_class() before selecting a specific CT clamp model.


Choosing an SCT-013 model

Within the SCT-013 family, five models are characterized on the current bench (codes {1, 2, 3, 4, 6}); codes 5 and 7 exist in the API and SPEC but are not yet validated and are rejected by the library client-side (pre-bus, with no I²C transaction).

code Model Current range Status Typical use
1 SCT-013-005 0…5 A ✅ characterized Small loads — lamps, low-power electronics, a single switch
2 SCT-013-010 0…10 A ✅ characterized One medium-power appliance — fridge, washing machine, air conditioner up to 2 kW
3 SCT-013-030 0…30 A ✅ characterized Mid-size household service entry — up to ~7 kW
4 SCT-013-050 0…50 A ✅ characterized Large service entry — electric heating, EV charger, single-family home with peak loads
5 SCT-013-100 0…100 A ⏳ uncharacterized (Main service entry; code reserved, requires bench validation.)
6 SCT-013-020 0…20 A ✅ characterized Medium service entry — 3–4 kW appliances, heavy household equipment
7 SCT-013-060 0…60 A ⏳ uncharacterized (Industrial sub-meter; code reserved, requires bench validation.)

Production-safe codes — {1, 2, 3, 4, 6}. Calling dev.set_ct_model_ch(ch, 5) or dev.set_ct_model_ch(ch, 7) (or passing such a code to dev.configure_channels(...)) raises RbAmpParamError — the library does not send the write to the device (client-side guard _validate_ct_code, REG_ERROR on the device stays 0x00).

Per-class accepted sets (v1.3 firmware): - RbAmpSensorClass.SCT_013{1, 2, 3, 4, 6} - RbAmpSensorClass.WIRED_CT{1, 2, 3} (factory preset slots) - RbAmpSensorClass.BUILTIN_CT (onboard CT, no codes)

Codes 0x06 and 0x07 are non-monotonic by rating (added after the original 0x01..0x05). Pick by the rating you need.

How to pick the right model

The basic rule:

  1. Determine the maximum current that can flow in the circuit (based on the largest load + 30% headroom).
  2. Choose the model whose range covers that value.
  3. Do not over-size by more than 5×. An SCT-013-100 clamp on a circuit with a maximum current of 5 A will work, but it gives low resolution and large error at typical values.

Headroom

An SCT-013 clamp operates without saturation within its rated range. Short-lived peaks (compressor inrush, inductive load) can exceed the rating by 5–7× — this is normal, the clamp physically withstands it, but measurement becomes non-linear above the rating.

If your load has a peak current above the clamp's rating, go one size up. For example, for a washing machine with a 12 A inrush current (and a 2–3 A rating during operation) SCT-013-030 is better than SCT-013-005.


How to tell the module about your choice

Two calls in the correct order are mandatory — first dev.set_sensor_class(), then dev.set_ct_model(). If you call dev.set_ct_model() before dev.set_sensor_class(), the package raises RbAmpModeError:

text
REG_SENSOR_CLASS is UNSET;
call dev.set_sensor_class(RbAmpSensorClass.SCT_013) first

CT model — a functional preset, not a label. Writing the CT model immediately applies the NF baseline, gain, and shape factor — the current readings change. Changing sensor_class resets CT_MODEL to its default and requires setting it again.

python
from rbamp import RbAmp, RbAmpSensorClass, RbAmpModeError
with RbAmp(bus, 0x50) as dev:
    # Step 1: sensor class. MANDATORY before set_ct_model().
    try:
        dev.set_sensor_class(RbAmpSensorClass.SCT_013)
    except RbAmpModeError as e:
        # Possible causes: communication failure (see 10 · Troubleshooting),
        # invalid argument (cls outside the known values)
        print("set_sensor_class failed:", e)
        return
    # Step 2: model within the family.
    # 1 = SCT-013-005, 2 = SCT-013-010, 3 = SCT-013-030,
    # 4 = SCT-013-050, 6 = SCT-013-020 (code 5 reserved).
    try:
        dev.set_ct_model(3)   # e.g. SCT-013-030
    except RbAmpModeError:
        print("Sensor class must be set first")
    except ValueError:
        print("Code not in per-class accept-set (SCT_013: {1,2,3,4,6})")

set_sensor_class() accepts either an enum or a plain int — both forms are equivalent:

python
dev.set_sensor_class(RbAmpSensorClass.SCT_013)  # explicit enum form
dev.set_sensor_class(1)                          # numeric (equivalent)

The package deliberately does NOT call set_sensor_class() on your behalf. If this step is skipped, set_ct_model() raises RbAmpModeError without writing to flash. This is by design, so that the behavior is predictable and explicit — no "magic" in the public API.

After these two calls:

  • The module saves both values to flash — the setting survives a reset, a power-cycle, and a firmware re-flash.
  • The calibration coefficients for that specific combination (sensor class + model) are loaded from the factory preset table. You do not need to touch any manual calibration registers.
  • The next read of dev.current[0] (or dev.read_current(0)) already returns a value in amperes with the correct scaling.

Total time for both calls is about 1.4 seconds (two flash-write operations × ~700 ms each, limited by the flash page erase time). It is done once at first installation; the setting is saved to flash and is not repeated again.

If you already chose the sensor on first run and you are simply restarting the script, you do not need to repeat the set_sensor_class() and set_ct_model() calls — the module remembers the previous choice. But there is no harm either — calling again with the same value just rewrites the same byte.

Verifying the setup

A simple sanity check after set_ct_model():

python
import time
from rbamp import RbAmp, RbAmpSensorClass
def sanity_check(dev):
    print("Ready. Connect a purely resistive load",
          "(e.g. an incandescent lamp).")
    print("Expect a stable PF ~= 1.0 and a positive P.")
    while True:
        u  = dev.voltage              # property — one I²C transaction
        i  = dev.read_current(0)
        p  = dev.read_power(0)
        pf = dev.read_power_factor(0)
        print(f"U={u:.1f} V  I={i:.2f} A  P={p:.1f} W  PF={pf:.2f}")
        time.sleep(2)
with RbAmp(bus, 0x50) as dev:
    dev.set_sensor_class(RbAmpSensorClass.SCT_013)
    dev.set_ct_model(3)
    sanity_check(dev)

On MicroPython, replace time.sleep(2) with time.sleep_ms(2000).

On a purely resistive load (incandescent lamp, electric kettle, heating element) you should expect:

  • U ≈ 220–240 V (for 230 V mains)
  • I ≈ matches the load power (P / U)
  • P > 0 and stable
  • PF ≈ 1.0 (definitely positive)

If something does not add up, see 10_troubleshooting.md.


Modules with multiple current channels

SKU lineup — what fits the task

SKU I channels U channel Typical use
UI1 1 yes One load with full power computation (P, PF)
UI2 2 yes Two independent loads on the same phase (service entry + a large consumer)
UI3 3 yes Roadmap — not shipping on the current MCU package (needs 4 ADC channels; described for forward-compat).
I1 1 no Sub-meter without power computation (current only)
I2 2 no Two sub-meters, or a dual-CT topology on a single line
I3 3 no Three sub-meters, or dual-CT + a third current channel

What each channel measures

  • U channel (UI only): U_rms, U_peak, frequency. One* per module.
  • I channels (all SKUs): each channel independently — I_rms, I_peak, P (active power), PF, avg_p per period.
  • I variants: I1/I2/I3 have no U channel — P/PF computation is not possible on the device (only I_rms per channel).
  • Single-phase module: the current UI2/I2/I3 are single-phase. All I channels must be on the same phase (or, for I variants, on the same phase as well if you want to compute P correctly master-side).

Per-channel CT model — independent calibration

On the UI2, I2, and I3 modules each current channel has an independent SCT-013 model selection. You can connect, for example, an SCT-013-005 on channel 0 (a single outlet), an SCT-013-030 on channel 1 (a stove line), and an SCT-013-020 on channel 2 (a medium feed — I3 only).

The API for per-channel selection is dev.set_ct_model_ch(channel, code):

python
dev.set_sensor_class(RbAmpSensorClass.SCT_013)   # once for all channels
# v1.3: binding order does NOT matter (Fix A pure-staging).
dev.set_ct_model_ch(0, 1)   # channel 0: SCT-013-005
dev.set_ct_model_ch(1, 3)   # channel 1: SCT-013-030
dev.set_ct_model_ch(2, 6)   # channel 2: SCT-013-020 (I3 only)

v1.3: channel binding order does not matter (Fix A pure-staging). On v1.3 writing REG_CT_MODEL (0x05) stages the value but no longer applies it automatically to ch0. Application happens only via CMD_SET_CT_MODEL_CHn. This means you can configure channels in any order — with no clobber.

The single-argument dev.set_ct_model(code) is a convenience form for single-channel SKUs (applied to channel 0). On multi-channel modules it is equivalent to dev.set_ct_model_ch(0, code).


Advanced setup: two clamps of different ratings on one wire

An additional pattern, not the basic one. This section describes an optional technique for improving resolution at low currents. For most installations a single clamp matched to the load range is sufficient. Use dual-CT only if you have a specific accuracy requirement at currents < 1 A.

When it applies

  • Multi-channel modules UI2 / I2 / I3 (at least 2 I channels).
  • The same wire needs to be measured both for small loads (≤ 1 A) and for peak events (≥ 5 A) with equal quality.
  • A typical example: an apartment service entry where during the day there is 50–100 W of standby, and in the evening — a kettle or a stove inrush at 3+ kW.

The idea

Two SCT-013 clamps of different ratings are installed on the same wire:

  • Channel 0 — the small clamp (e.g. SCT-013-005, 5 A): sees small currents with better resolution and a lower noise floor.
  • Channel 1 — the large clamp (e.g. SCT-013-030 or higher): handles currents above the small clamp's overload point without saturation.

The master itself chooses which channel to use depending on the current value — while the small clamp is in its linear range, its reading is more accurate; once it is exceeded, it switches to the large one.

Configuration (order-independent on v1.3)

First the sensor class once, then the models per channel in any order. On v1.3 firmware (Fix-A pure-staging), writing REG_CT_MODEL (0x05) only stages the value; binding to a specific channel happens exclusively via the per-channel CMD_SET_CT_MODEL_CHn opcode. The legacy "descending order" workaround required on v1.2 firmware is no longer needed.

python
dev.set_sensor_class(RbAmpSensorClass.SCT_013)   # once
# Any order is valid on v1.3 — each call binds its own channel.
dev.set_ct_model_ch(0, 1)   # ch0 = SCT-013-005 (0..5 A)
dev.set_ct_model_ch(1, 3)   # ch1 = SCT-013-030 (0..30 A)

Final state: ch0 = SCT-013-005, ch1 = SCT-013-030. ✓

Aggregation logic on the master side

The simplest pattern is to switch on a threshold:

python
import math
def read_combined_current(dev):
    """Read the combined current — picks low-CT when in its linear range,
    otherwise falls back to the high-CT.
    """
    i_low  = dev.read_current(0)   # the small clamp
    i_high = dev.read_current(1)   # the large clamp
    # While the small clamp is far from saturation, it gives better
    # accuracy at low currents. Switch to the large one when
    # approaching the overload point.
    #
    # The 4.5 A threshold for SCT-013-005 is PROVISIONAL; the exact
    # value will be determined by bench validation (see below).
    # Behavior in the vicinity of the threshold is a matter of
    # measurement, not estimation.
    if not math.isnan(i_low) and i_low < 4.5:
        return i_low
    return i_high

Dual-CT install: two clamps on one L wire (low-range + high-range), both arrows toward the load

Bench validation. The exact figures of the dual-CT pattern (behavior in the vicinity of the threshold, temperature drift, the divergence of the two clamps in the overlapping range) are established by the factory bench-validation program . Until it is complete, treat dual-CT as a pilot pattern; for critical applications a single clamp matched to the upper end of the load range is preferable.

Approaches to improving sensitivity at low currents

If your load has a large dynamic range (for example, 1 W of standby for a router vs a 2000 W water heater on the same outlet), a single clamp sized for the upper limit loses the lower currents in the noise.

Three strategies in increasing order of complexity:

  1. Size the CT for the maximum, not "with headroom". The most common mistake is to put an SCT-013-100 (100 A) on a home outlet with a typical consumption of 0.5–10 A. The signal sits in the lower 1–10% of the ADC — where noise becomes comparable to the signal. For a household scenario (16 A outlet) SCT-013-030 is optimal; for connecting a single device (≤ 5 A) — SCT-013-005.
  2. Dual-CT topology (requires a UI2/UI3 SKU): a small clamp on the lower range + a large one on the upper, with the master choosing by threshold. See the "Dual-CT topology" section above — the pattern is a pilot one, the numbers are being refined by the factory bench-validation program.
  3. Bench calibration of the noise floor (factory-side): the factory bench-calibration program characterizes the noise floor on the test bench; the results are baked into the firmware's calibration array. On the user side, there is nothing to do beyond set_sensor_class() + set_ct_model(). Until the program is complete, the specific low-current accuracy figures are not published.

Production vs Develop mode (persistence reference)

The rbAmp module operates in two modes, differing in what exactly is saved to flash.

Command (opcode) Production Persists
CMD_SAVE_USER_CONFIG (0x32) OK ct_model / sensor_class / per-channel CT / fleet_config / group_id / label
CMD_COMMIT_ADDR (0x30, magic-armed) OK I²C address (two-phase address commit, see 04 · Wiring)
CMD_RESET (0x01) ✅ OK — (software reset)
CMD_LATCH_PERIOD (0x27) ✅ OK — (period snapshot)
CMD_CLEAR_ERROR ✅ OK
CMD_SAVE_GAINS (0x26) BLOCKED in production (returns DEV_ERR_PARAM; reboot reverts) — factory-only gains / NF / phase (factory cal)
CMD_FACTORY_RESET BLOCKED in production

In production mode, writes of factory calibration are rejected by the firmware — protection against accidentally erasing the factory coefficients.

Read-back ≠ persistence (v1.3 A7 HW-verified). The production guard accepts the write into RAM (a subsequent read returns what was written), but the flash-save may be rejected. The only valid way to confirm persistence is to reboot the module via CMD_RESET and read again:

python dev.set_ct_model(code) dev.reset() # CMD_RESET 0x01, works in production time.sleep(0.3) # boot complete (300 ms canonical) check = dev.read_reg(0x05) assert check == code # ONLY now is persistence confirmed

The address is an exception (v1.3 A2 Fix 4): REG_I2C_ADDRESS reads the active address at boot. After staging it echoes the candidate until CMD_COMMIT_ADDR + reset.

Cross-link: 09 · API reference — details on specific opcodes, 10 · Troubleshooting — what to do if persistence is not confirmed.


What's next