Three-Phase Energy Monitoring in Home Assistant: 3× rbAmp UI on One ESP32

Coherent per-phase 3-phase energy monitoring in Home Assistant: three rbAmp UI modules on one ESP32 over I²C, with wiring and the full ESPHome config.

What you'll build

  • Real per-phase voltage, current, active power, energy (kWh) and power factor for L1 / L2 / L3.
  • A coherent three-phase total active power (the three phases summed on one synchronized latch).
  • Everything on one ESP32 over a single I²C bus — no second microcontroller, no round-robin ADC.
  • All of it in the Home Assistant Energy Dashboard.

Bill of materials

Item Qty Notes
rbAmp BASIC SCT-UI1 3 one per phase — voltage + current + on-chip real power · product
SCT-013 current transformer 3 one per phase, rating to match each phase's service capacity · product
ESP32 dev board 1 any esp32dev-class board
Jumper wires — the shared I²C bus (SDA/SCL/3V3/GND)
Safety

Each UI1 module needs its own phase voltage as well as its CT. Wire each module's voltage input to the phase it's metering (L1→module A, L2→module B, L3→module C) — that per-phase voltage pairing is exactly what makes the measurement coherent. Read the safety section below before you wire anything — the voltage taps are live-conductor connections, not clip-on clamps.

Safety first — the voltage taps are live-conductor work

Safety

⚠️ This build also connects voltage inputs to mains. Each module's voltage input connects to a live phase (L) and neutral, with a fuse in L as the module docs specify. The current side stays non-invasive: the SCT-013 clamps around its phase conductor — you never cut or strip a live wire. Label every CT and voltage lead to its phase. For work inside an electrical panel, call a qualified electrician.

Wire the bus

All three modules share one I²C bus off the ESP32:

Text
ESP32 GPIO21 (SDA) ─┬── UI1 phase-A  (CT on L1, voltage tap on L1)
                    ├── UI1 phase-B  (CT on L2, voltage tap on L2)
                    └── UI1 phase-C  (CT on L3, voltage tap on L3)
ESP32 GPIO22 (SCL) ─┘   + shared 3V3 and GND to all three
  • Clamp each module's CT around one phase conductor, arrow toward the load.
  • On-board pull-ups: keep them active on the first module in physical wire order and disable them on the other two — one pull-up pair per bus, never external. (See the module hardware doc.)

Give each module its own address

All modules ship at I²C address 0x50. Three on one bus need three addresses — 0x50, 0x51, 0x52. Assign the second and third once each, one module at a time with the others disconnected so there's no clash. On current firmware this is a production-mode operation — no factory mode, no extra tools:

  1. Connect only the module you're re-addressing.
  2. Flash a scratch config with address: 0x50 and new_address: 0x51 (then 0x52 for the third).
  3. Watch the ESPHome boot log confirm the change, then set address: 0x51, delete the new_address: line, and move on to the next module.

(Full mechanics: ESPHome API reference → new_address.)

The ESPHome config

Three UI1 modules at 0x50 / 0x51 / 0x52, one synchronized fleet, live per-phase data plus the coherent total. Set your CT sizes and Wi-Fi secrets, flash:

YAML
# Three-phase energy monitoring: 3× rbAmp UI1 on one ESP32, one I²C bus.
#   GPIO21 SDA ─┬─ UI1 @0x50  (phase A: V+I on L1)
#              ├─ UI1 @0x51  (phase B: V+I on L2)
#              └─ UI1 @0x52  (phase C: V+I on L3)
# Each module computes its phase's real power on-chip; fleet_gc_enable + group_id
# latch all three on one broadcast instant (<10 µs skew).
# Compile-verified: ESPHome 2026.5.3, github://rb-amp/rbamp-esphome@v1.4.0.

esphome:
  name: rbamp-3phase

esp32:
  board: esp32dev
  framework:
    type: arduino

wifi:
  ssid: !secret wifi_ssid
  password: !secret wifi_password

api:
ota:
  - platform: esphome
logger:

i2c:
  sda: GPIO21
  scl: GPIO22
  frequency: 50kHz   # ESP-IDF i2c_master driver + the module's I²C recovery window interact at
                     # 100 kHz → intermittent read NACKs on ESP32. 50 kHz is the robust setting.
                     # STM32 / RP2040 / Linux-SBC masters run this module at 100 kHz fine.
  scan: true

external_components:
  - source: github://rb-amp/rbamp-esphome@v1.4.0
    components: [rbamp]

# ─── Three UI1 modules in the same GC-LATCH fleet ────────────────────────────
rbamp:
  - id: phase_a
    address: 0x50
    update_interval: 10s
    latch_interval: 60s
    ct_model: SCT_013_050         # mains phase — pick to match your service capacity
    fleet_gc_enable: true
    group_id: 1
  - id: phase_b
    address: 0x51
    update_interval: 10s
    latch_interval: 60s
    ct_model: SCT_013_050
    fleet_gc_enable: true
    group_id: 1
  - id: phase_c
    address: 0x52
    update_interval: 10s
    latch_interval: 60s
    ct_model: SCT_013_050
    fleet_gc_enable: true
    group_id: 1

# ─── HA entities — per-phase real V/I/P/Wh/PF + 3-phase total ────────────────
sensor:
  # ══ Phase A (L1) ═════════════════════════════════════════════════════════
  - platform: rbamp
    rbamp_id: phase_a
    voltage:
      name: "Phase A Voltage"
    current:
      name: "Phase A Current"
    power:
      name: "Phase A Power"
      id: p_phase_a
    energy:
      name: "Phase A Energy"                  # ← per-phase kWh accumulator
    power_factor:
      name: "Phase A Power Factor"
    frequency:
      name: "Phase A Frequency"               # publish freq from phase A only

  # ══ Phase B (L2) ═════════════════════════════════════════════════════════
  - platform: rbamp
    rbamp_id: phase_b
    voltage:
      name: "Phase B Voltage"
    current:
      name: "Phase B Current"
    power:
      name: "Phase B Power"
      id: p_phase_b
    energy:
      name: "Phase B Energy"
    power_factor:
      name: "Phase B Power Factor"

  # ══ Phase C (L3) ═════════════════════════════════════════════════════════
  - platform: rbamp
    rbamp_id: phase_c
    voltage:
      name: "Phase C Voltage"
    current:
      name: "Phase C Current"
    power:
      name: "Phase C Power"
      id: p_phase_c
    energy:
      name: "Phase C Energy"
    power_factor:
      name: "Phase C Power Factor"

  # ── 3-phase total active power (Σ per-phase real P) ───────────────────────
  # All three modules latch on the same broadcast instant (fleet_gc_enable),
  # so the summed instantaneous P values are coherent. Reads happen
  # sequentially after the latch, but the frozen P values reflect the same
  # wire moment. Skew: <10 µs chip-side; negligible for any real load.
  - platform: template
    name: "Total 3-Phase Active Power"
    device_class: power
    state_class: measurement
    unit_of_measurement: W
    accuracy_decimals: 1
    update_interval: 10s
    lambda: |-
      float total = 0;
      if (id(p_phase_a).has_state()) total += id(p_phase_a).state;
      if (id(p_phase_b).has_state()) total += id(p_phase_b).state;
      if (id(p_phase_c).has_state()) total += id(p_phase_c).state;
      return total;

Two knobs worth understanding:

  • fleet_gc_enable: true + group_id: 1 put all three modules in one synchronized fleet. Once a minute the ESP32 sends a single General-Call "latch now" frame and every module freezes its period accumulator on the same instant (sub-10-µs skew) — that's what makes the three-phase total coherent instead of three independently-sampled numbers.

  • latch_interval: 60s (rbAmp ESPHome v1.4) decouples the synchronized LATCH from the live read cadence: the dashboard refreshes voltage / current / power every update_interval (10 s), while the coherent energy-latch burst runs just once a minute. kWh stays exact either way — the master integrates over real wall-clock time. Drop the line for single-cadence v1.3 behaviour.

Add it to Home Assistant

  1. Flash and let the node come up — Home Assistant auto-discovers it via the ESPHome API. You'll see the per-phase entities plus Total 3-Phase Active Power.

  2. Settings → Devices & Services → Energy. Add each phase's Energy sensor (Phase A/B/C Energy) as a grid-consumption source — the dashboard sums them for whole-home consumption.

  3. Build a quick Lovelace view with the three per-phase powers and the total for a live per-circuit picture.

Verify it's wired right

  • The boot log's I²C scan should list all three addresses:
Text
[i2c] Found i2c device at address 0x50
[i2c] Found i2c device at address 0x51
[i2c] Found i2c device at address 0x52
  • Under a known single-phase load on one phase, only that phase's power should move.
  • The three per-phase powers should sum to Total 3-Phase Active Power at every update.
  • If a phase reads a suspiciously round fraction of what you expect, check that its voltage tap is on the same phase as its CT — the coherent pairing is the whole point (see the physics).

Why this is accurate

Each module measures its phase's voltage and current together and computes real active power on-chip; the synchronized latch freezes all three on one instant. That's coherent per-phase integration — the sub-1% tier, versus the 15–50% error of measuring one phase and tripling it. The full reasoning is in the companion article: why three single-phase meters can't measure your 3-phase power.

Prefer one board? A dedicated single-board variant (U3I3 — all three phases on one board, one I²C address) is in development. It's on the roadmap, not shipping yet; subscribe below and we'll say when it lands. Until then, this three-module fleet is the honest-numbers path you can build today.