Period Metering and Tariff Accounting

For tariff energy accounting (Wh per 1 min / 15 min / 1 hour / day / month / year) rbAmp provides an atomic period latch mechanism: a single I²C command freezes the time-averaged power over a period, and the master multiplies it by its own wall-clock dt to get Wh.

This is the production-grade way to extract energy data. The alternative — integrating RT P_real on the master side every 200 ms — yields the same result on BASIC, but keeps the master continuously active.


Why period latch is needed

A single time base, owned by the master

In a multi-module system the time base must live on the master. The chip therefore does not integrate Wh internally. Instead:

  • The chip exposes a time-independent statistic — the average P over the period.
  • The master multiplies it by its own wall-clock dt.
  • All modules share the same time reference → no drift accumulates in the system-wide energy total.

The formula

plaintext
E_Wh = avg_P_W × master_dt_seconds / 3600

Where:

  • avg_P_W — the value of PERIOD_AVG_P_W, read after CMD_LATCH_PERIOD.
  • master_dt_seconds — the seconds elapsed between two successive latches, measured by the master.

Atomic period latch — concept

What the command does

Writing 0x27 to REG_COMMAND = 0x01 triggers an atomic sequence inside the firmware (executed under __disable_irq()):

plaintext
1. snapshot ← live      (copy the live accumulator into the I²C-visible snapshot)
2. live     ← 0         (reset the accumulator; start the next period)
3. period_start_ms = now

These three steps are indivisible — neither the I²C ISR nor the ADC ISR can interleave between them. This guarantees:

  • Atomicity: every per-window P sample belongs to exactly one snapshot — either the previous one or the next one — never duplicated, never lost.
  • No gap: the new period begins at the same instant the previous one ended — there is no blind interval.

Where the snapshot lives

After a latch, reads from 0xDC..0xEF and 0xC2..0xC9 return the just-closed period. The live accumulator already starts counting the next period, but those registers update only on the next latch.

One write — closes and opens

This is the defining property of the rbAmp latch. A single LATCH command simultaneously:

  • Closes the period that just ended (its data → snapshot)
  • Opens the next period (live ← 0)

The master needs one write per measurement, not two (as in a naive "start → stop → read" implementation).


plaintext
master                          chip
------                          ----
                                accumulator running since boot...
write CMD_LATCH (0x27)   ────►  snapshot ← live (since-boot — DISCARD)
                                live ← 0, period_start = T0
t0 = master.clock()      ◄──── first latch — primer (discard)
  [wait 60 seconds]
write CMD_LATCH          ────►  snapshot ← live (over [T0..T1] — KEEP)
                                live ← 0, period_start = T1
t1 = master.clock()
read avg_p_W @ 0xDC      ────►  float32 LE
E1_Wh = avg_p × (t1 − t0) / 3600
  [wait 60 seconds]
write CMD_LATCH          ────►  snapshot ← live (over [T1..T2] — KEEP)
                                live ← 0, period_start = T2
t2 = master.clock()
read avg_p_W
E2_Wh = avg_p × (t2 − t1) / 3600
...and so on. t1 is both the end of period 1 and the start of period 2.

The first latch is a primer (discard)

The first latch after boot captures whatever the accumulator collected from power-on until the master's first call — an undefined-length window unsuitable for billing. Discard its result. From the second latch onward, data is clean and usable.


Period snapshot registers

Address Name Type When to read Description
0x07 PERIOD_VALID u8 read first bit0 = 1 if snapshot is fresh and valid, 0 if stale (race or premature latch)
0xDC..0xDF PERIOD_AVG_P_W[0] float32 LE primary PRODUCTION — mean P_real of channel I0 over the period (W)
0xC2..0xC5 PERIOD_AVG_P_W[1] float32 LE UI2/UI3 Mean P_real of channel I1
0xC6..0xC9 PERIOD_AVG_P_W[2] float32 LE UI3 Mean P_real of channel I2
0xE0..0xE3 PERIOD_MAX_P_W float32 LE optional Peak P_real during the period (for demand tariffs)
0xEC..0xEF PERIOD_LATCH_MS u32 LE diagnostic Chip's view of dt between latches (compare with master dt)
0xBE..0xC1 PERIOD_COMMIT_COUNT u32 LE diagnostic Number of RT windows that landed in this period

STANDARD / PRO additions for bidirectional accounting

Address Name Type Description
SKU-specific PERIOD_AVG_P_NEG_W[0] float32 LE Mean export power for channel I0 over the period (W, ≥ 0 in magnitude) — STANDARD/PRO only
SKU-specific PERIOD_AVG_P_NEG_W[1..2] float32 LE Same for channels I1, I2 — STANDARD/PRO only

The numeric addresses of PERIOD_AVG_P_NEG_W[0..2] are documented in the SKU datasheet of the STANDARD/PRO product — they live above 0xCF in tier-specific extension registers, not in the base block. On BASIC modules these registers do not exist (NACK on read). Master code that targets all tiers should treat NACK as "no bidirectional support" and fall back to RT-based accounting.


Master-side algorithm

Basic cycle (one module, 60-second period)

cpp
#include <Wire.h>
#define RB_ADDR 0x50
void setup() {
  Serial.begin(115200);
  Wire.begin();
  delay(300);
  // 1. Primer latch (discard result)
  rb_write_u8(RB_ADDR, 0x01, 0x27);
}
void loop() {
  static uint32_t t_prev = millis();
  delay(60000);                                    // wait 60 seconds
  // 2. Final latch — closes [t_prev, now]
  rb_write_u8(RB_ADDR, 0x01, 0x27);
  uint32_t t_now = millis();
  delay(50);                                       // firmware finishes in ~5 ms; allow margin
  // 3. Check PERIOD_VALID
  uint8_t valid = rb_read_u8(RB_ADDR, 0x07);
  if ((valid & 0x01) == 0) {
    // Race or premature latch — retry
    delay(250);
    rb_write_u8(RB_ADDR, 0x01, 0x27);
    t_now = millis();
    delay(50);
    valid = rb_read_u8(RB_ADDR, 0x07);
    if ((valid & 0x01) == 0) {
      Serial.println("WARN: two stale latches in a row");
      t_prev = millis();
      return;
    }
  }
  // 4. Read the snapshot
  float avg_p = rb_read_float_le(RB_ADDR, 0xDC);
  float max_p = rb_read_float_le(RB_ADDR, 0xE0);
  // 5. Compute energy on master clock
  float dt_s = (t_now - t_prev) / 1000.0f;
  float e_wh = avg_p * dt_s / 3600.0f;
  Serial.printf("[+%5.1fs] E=%.3f Wh  avg_P=%.1f W  max_P=%.1f W\n",
                dt_s, e_wh, avg_p, max_p);
  t_prev = t_now;
}

What is essential in this code

  1. First latch is a primer — its result is discarded.
  2. PERIOD_VALID is read BEFORE using the snapshot — otherwise stale data can leak through on a race.
  3. dt is measured on the master, not derived from PERIOD_LATCH_MS — the chip register is only for drift diagnostics.
  4. t_prev updates to the t_now of a successful latch, not to the original period start — this keeps the chain seamless without gaps.

Bidirectional accounting (STANDARD / PRO)

This section applies to STANDARD and PRO product tiers only. On a BASIC module, PERIOD_AVG_P_NEG_W registers do not exist (NACK), and PERIOD_AVG_P_W is always ≥ 0 (negative samples are dropped from the accumulator).

What bidirectional accounting means

The chip integrates two separate accumulators per period:

  • Consumption: integral of max(P, 0) × dt — positive power only.
  • Export: integral of max(−P, 0) × dt — negative power only, by magnitude.

The sum of both gives the total energy that passed through the meter in absolute terms; the difference is the net consumption (what a mechanical disc meter would show).

Applications

  • Homes with solar panels: consumption and export are billed under different tariffs (feed-in tariff)
  • Systems with battery storage: tracking charge/discharge cycles
  • Wind turbines, regenerative loads, V2G EV chargers

Registers (STANDARD / PRO)

Address Name Description
0xDC PERIOD_AVG_P_W[0] Mean consumption P (≥ 0), as on BASIC
(SKU-specific) PERIOD_AVG_P_NEG_W[0] Mean export P (≥ 0 in magnitude)

Algorithm for STANDARD / PRO

⚠️ The constant below is a sentinel — do NOT copy verbatim. The real address of PERIOD_AVG_P_NEG_W[0] is SKU-specific and lives above 0xCF. Note that 0xD0 in the base register map is Q0_reac (reactive power) — reading from 0xD0 will silently return reactive power instead of export power, producing wrong billing data. Always pull the correct address from the STANDARD/PRO SKU datasheet before flashing this code.

cpp
// Bidirectional accounting, 60-second period
#define REG_PERIOD_AVG_P_NEG 0xFF   // SENTINEL — replace with SKU-datasheet address before use
void loop() {
  static uint32_t t_prev = millis();
  delay(60000);
  rb_write_u8(RB_ADDR, 0x01, 0x27);
  uint32_t t_now = millis();
  delay(50);
  if ((rb_read_u8(RB_ADDR, 0x07) & 0x01) == 0) {
    t_prev = millis();
    return;
  }
  float avg_p_consume = rb_read_float_le(RB_ADDR, 0xDC);                  // ≥ 0
  float avg_p_export  = rb_read_float_le(RB_ADDR, REG_PERIOD_AVG_P_NEG);  // ≥ 0
  float dt_s = (t_now - t_prev) / 1000.0f;
  float e_consume_wh = avg_p_consume * dt_s / 3600.0f;
  float e_export_wh  = avg_p_export  * dt_s / 3600.0f;
  float e_net_wh     = e_consume_wh - e_export_wh;
  Serial.printf("[%.1fs] consume=%.3f Wh  export=%.3f Wh  net=%+.3f Wh\n",
                dt_s, e_consume_wh, e_export_wh, e_net_wh);
  t_prev = t_now;
}

What is not available on BASIC

If you own a BASIC-tier module and need bidirectional accounting, you have two options:

  1. Master-side integration — read RT P_real (0xA6) every ~200 ms and integrate positive and negative samples separately on the master side. Accuracy is slightly lower (due to sampling discretisation), but works on any firmware.
  2. Upgrade the hardware to a STANDARD or PRO product tier. Contact your supplier — bidirectional support is a hardware + firmware combination, not a firmware-only flag.

I-only variants — period metering returns zero

On I1/I2/I3 (and higher I*-only variants) without a voltage sensor:

  • PERIOD_AVG_P_W[*] is always 0.0f — no U means there is nothing to integrate.
  • PERIOD_VALID still reports 1 (the snapshot is valid, just zero).
  • PERIOD_MAX_P_W is also 0.

For I-only variants the on-chip period metering does not deliver an energy reading. The master must either:

  • Use its own voltage sensor and integrate I_rms × U_master × cos(φ)_master (more complex; requires phase synchronisation), or
  • Use the I-only module only for current-presence monitoring, and pair it with a UI* module or an external meter for energy.

Event-driven vs periodic polling

Periodic (cron-style)

The master reads every N seconds on a timer. Arduino has no built-in setInterval; use a millis()-based pattern or a scheduler library (Ticker on ESP8266/ESP32, TaskScheduler):

cpp
// Once per hour, using millis() — wrap-safe via unsigned subtraction.
static uint32_t t_last_period = 0;
void loop() {
  uint32_t now = millis();
  if (now - t_last_period >= 3600UL * 1000UL) {
    t_last_period = now;
    rb_write_u8(0x50, 0x01, 0x27);
    // ... read snapshot, accumulate Wh
  }
}

Suitable for classical billing (1-min, 15-min, 1-hour).

Event-driven

The master issues a latch when an external event occurs:

  • A pulse from the utility's electronic meter (cross-check)
  • A tariff change (peak / off-peak)
  • A user query ("how much have I used so far?")
cpp
void on_tariff_change() {
  rb_write_u8(0x50, 0x01, 0x27);    // close the period under the old tariff
  delay(50);
  if (rb_read_u8(0x50, 0x07) & 0x01) {
    float avg_p = rb_read_float_le(0x50, 0xDC);
    save_period_to_tariff_a_bucket(avg_p, current_dt_s);
  }
  // the next period accumulates into bucket B
}

Restarting the period

To discard the live accumulator and start fresh, issue an extra latch and ignore its result:

cpp
void restart_period() {
  rb_write_u8(0x50, 0x01, 0x27);    // close current + start new
  // do not read the snapshot — discard
}

After this, resume a normal latch cycle from scratch.


Multi-module — simultaneous latch

If the master wants synchronous snapshots from all modules (for an instantaneous house energy balance), there are two approaches.

Approach 1 — sequential latch (simple)

The master latches each module in turn:

cpp
const uint8_t modules[] = {0x50, 0x51, 0x52};
uint32_t t_prev[] = {0, 0, 0};
void setup() {
  Wire.begin();
  // Primer
  for (int i = 0; i < 3; i++) {
    rb_write_u8(modules[i], 0x01, 0x27);
    t_prev[i] = millis();
  }
}
void loop() {
  delay(60000);
  for (int i = 0; i < 3; i++) {
    rb_write_u8(modules[i], 0x01, 0x27);
    uint32_t t_now = millis();
    delay(50);
    if (rb_read_u8(modules[i], 0x07) & 0x01) {
      float avg_p = rb_read_float_le(modules[i], 0xDC);
      float dt_s = (t_now - t_prev[i]) / 1000.0f;
      float e_wh = avg_p * dt_s / 3600.0f;
      Serial.printf("[0x%02X] E=%.3f Wh\n", modules[i], e_wh);
      t_prev[i] = t_now;
    }
  }
}

Downside: latch instants differ by a few milliseconds. For a 60-second period this yields < 0.1 % error — negligible.

Approach 2 — broadcast latch via general call (precise)

The I²C general-call address 0x00 is a packet that all slaves receive simultaneously. rbAmp listens for general-call frames and recognises CMD_LATCH_PERIOD = 0x27. All modules latch their snapshot at the same instant:

cpp
void broadcast_latch() {
  Wire.beginTransmission(0x00);     // general call
  Wire.write(0x01);                  // REG_COMMAND
  Wire.write(0x27);                  // CMD_LATCH_PERIOD
  Wire.endTransmission();
}

After the broadcast latch the master reads each module's snapshot by its individual address:

cpp
const uint8_t modules[] = {0x50, 0x51, 0x52};
uint32_t t_prev;
void setup() {
  Wire.begin();
  broadcast_latch();
  t_prev = millis();
}
void loop() {
  delay(60000);
  broadcast_latch();
  uint32_t t_now = millis();
  delay(50);
  float dt_s = (t_now - t_prev) / 1000.0f;
  for (int i = 0; i < 3; i++) {
    if (rb_read_u8(modules[i], 0x07) & 0x01) {
      float avg_p = rb_read_float_le(modules[i], 0xDC);
      float e_wh = avg_p * dt_s / 3600.0f;
      Serial.printf("[0x%02X] E=%.3f Wh  P_avg=%.1f W\n",
                    modules[i], e_wh, avg_p);
    }
  }
  t_prev = t_now;
}

Advantage: precise synchronisation — snapshots are taken at the same instant across all modules, within a few microseconds.

Use case: critical for instantaneous balancing (for example house_consume − solar_export at one moment in time).

Broadcast latch is available from firmware release 1.0 onward. CMD_RESET is also supported via general call. Other address-specific commands are ignored on general call.


Choosing the period length

Application Recommended dt
Live UI dashboard 1 s (or read RT P_real directly)
Trend chart, 1-minute resolution 60 s
15-minute peak-demand metering 900 s
Hourly billing 3600 s
Daily totals Accumulate hourly latches on the master; do not let a single period exceed 1 hour

Periods longer than 1 hour are allowed, but for very long periods the per-window accumulator can in principle overflow under extreme worst-case loads. For domestic loads ≤ 15 kW and periods ≤ 1 hour there is no overflow risk; for larger loads, prefer shorter periods.


PERIOD_MAX_P_W — peak demand

Register 0xE0 reports the maximum power observed in any RT window inside the period. Uses:

  • Peak-demand tariffs: utilities bill the highest 15-minute demand of the month for capacity charges.
  • Inrush detection: motor starts produce a 5–10× nominal spike — max_P >> avg_P flags the event.
  • Sanity check: if max_P greatly exceeds avg_P, the load is bursty — normal for many household scenarios, but a flag worth investigating if the load is expected to be steady.

Atomicity is guaranteed

CMD_LATCH_PERIOD runs with interrupts disabled during the snapshot copy (a few microseconds). The master can never read a half-updated snapshot — even if the master reads bytes immediately after the write, the firmware finishes updating the block before the next I²C transaction completes (at least 10+ µs elapse between write and read).

The same atomicity ties the accumulator reset to the snapshot copy — every P sample is in exactly one snapshot (either the previous period or the next one), never both, never neither.


What the master must NOT do

  • Do not compute U_rms × I_rms × dt — that is apparent energy (VAh), not Wh. Apparent power includes reactive content and overcharges any inductive load. Use PERIOD_AVG_P_W.
  • Do not infer direction from I_rms — RMS is always ≥ 0. Direction lives in the sign of P_real.
  • Do not use PERIOD_LATCH_MS for Wh — that register is diagnostic and may drift with the chip clock. master_dt is authoritative.
  • Do not latch too often (< 250 ms apart) — at least one RT window must complete between latches, otherwise the snapshot is empty (PERIOD_VALID = 0).

Clock-drift diagnostics

PERIOD_LATCH_MS reports dt as seen by the chip clock. The master can cross-check:

cpp
// Read u32 LE manually — rbAmp has NO pointer auto-increment, so each
// byte requires its own transaction with an explicit register address.
uint32_t rb_read_u32_le(uint8_t addr, uint8_t reg) {
  uint32_t v = 0;
  for (int i = 0; i < 4; i++) {
    v |= ((uint32_t)rb_read_u8(addr, reg + i)) << (8 * i);
  }
  return v;
}
uint32_t chip_dt   = rb_read_u32_le(0x50, 0xEC);
uint32_t master_dt = t_now - t_prev;            // uint32 subtraction is wrap-safe — do not cast to int32
float ratio = (float)chip_dt / (float)master_dt;
if (ratio < 0.95f || ratio > 1.05f) {
  Serial.printf("WARN: chip clock drift, ratio=%.3f\n", ratio);
}

This does not affect Wh accuracy (Wh uses the master clock), but it surfaces chip-clock or thermal-drift issues for fleet QA.


Next