03 · Current Sensor Selection

CT clamp installation: clamp the L wire only, arrow pointing toward the load

rbAmp measures current through an external CT clamp (current transformer) and voltage through a built-in voltage transformer (on UI* SKUs). This chapter is about how to pick the clamp for your load and how to tell the module which model is installed via YAML.


Sensor Family (sensor_class:)

The module's hardware revision determines which current-sensor family is supported. On current SKUs only one is available:

Class YAML value State
SCT-013 (split-core CT) SCT_013 Available now, default
WIRED_CT (wired CT) WIRED_CT Reserved for future SKUs
BUILTIN_CT (built-in shunt) BUILTIN_CT Reserved for future SKUs

The class is set once and stored in the module's flash:

yaml
rbamp:
  id: meter1
  sensor_class: SCT_013   # defaults to SCT_013, can be omitted

On firmware v1.2+, this value becomes a precondition for writing the CT model: the module will refuse if the class is not set. On earlier firmware the value is accepted by the schema and applied automatically on upgrade.

Read-compare-write boot writeback (v1.3+)

Starting with v1.3, on boot the component reads the current REG_SENSOR_CLASS (0x25) and compares it with the YAML-requested value. If they match, the flash write does not happen. This means:

  • The YAML block can keep sensor_class: SCT_013 forever — a repeat boot does not trigger a flash erase (~0 ms instead of ~700 ms).
  • The old advice to "remove sensor_class: from YAML after the first boot" is obsolete — the config is idempotent.

The same behavior applies to ct_model: / ct_models: (see below).

What "reserved" means for WIRED_CT and BUILTIN_CT — the component's schema accepts both values today (the YAML validates, no cv.Invalid is raised). However, no current rbAmp hardware revision physically supports them: the module will accept writing the class to the register, but without the matching front-end (WIRED_CT — a copper resistive shunt on the conductor bar; BUILTIN_CT — a built-in toroidal CT on the module board) the readings will bear no relation to reality.

For production deployments today, choose only SCT_013 (or omit the key — that is the default). Declaring WIRED_CT / BUILTIN_CT without the matching hardware is an anti-pattern that the component does not detect and will not warn about.

These classes will enter the production documentation after the release of the rbAmp-WiredCT / rbAmp-BuiltinCT SKUs — watch 11_changelog.md.


Choosing the SCT-013 Model

The module accepts any of the five production-ready models in the SCT-013 series. Their electrical output differs, so the module needs to know which one is installed — the factory coefficients are loaded for the specific model.

Code YAML name Rated current Typical load Maximum at 230 V v1.3 status
1 SCT_013_005 5 A LED lighting, single appliances, laptops ~1.15 kW production
2 SCT_013_010 10 A Desktop PCs, small AC unit, single circuit ~2.3 kW production
6 SCT_013_020 20 A Water heaters, medium branches, ~3-5 kW ~4.6 kW production (new in v1.3)
3 SCT_013_030 30 A Whole-home metering at typical consumption ~6.9 kW production (default SKU)
4 SCT_013_050 50 A EV charging, large AC unit, induction hob ~11.5 kW production
5 100 A (formerly SCT_013_100) ~23 kW reserved — unavailable in v1.3
7 60 A (previously undeclared; no characterization) uncharacterized

What happened to SCT_013_100? Code 5 in v1.3 firmware is reserved and returns DEV_ERR_PARAM on a write attempt. If the YAML had SCT_013_100, esphome config will reject the config with a hint listing the allowed values. For markets that need > 50 A (three-phase panels, commercial distribution), watch for the WIRED_CT SKU release or use several channels with SCT_013_050 in parallel.

The burden resistor is already installed on the module board — no external resistors between the clamp's output leads need to be added.

Selection Tree

plaintext
Peak continuous current through the conductor:
  |
  +-- ≤ 5 A    (LED, single appliances, ≤ 1.15 kW)
  |       → SCT_013_005    [code 1]
  |
  +-- 5..10 A  (PCs, small loads, ≤ 2.3 kW)
  |       → SCT_013_010    [code 2]
  |
  +-- 10..20 A (water heaters, branches, ≤ 4.6 kW)
  |       → SCT_013_020    [code 6, new in v1.3]
  |
  +-- 20..30 A (whole UK/EU home, ≤ 6.9 kW)
  |       → SCT_013_030    [code 3, default SKU]
  |
  +-- 30..50 A (EV, large AC unit, ≤ 11.5 kW)
  |       → SCT_013_050    [code 4]
  |
  +-- > 50 A   (panels, commercial)
          → several SCT_013_050 in parallel (split into channels)
            or the WIRED_CT SKU (roadmap)

General rule: choose the clamp with the lowest rating whose maximum measurable value covers the peak load with a ~30% margin. An oversized rating on a small load lowers the signal amplitude relative to noise — accuracy drops. A clamp rated below the peak will saturate the magnetic core and give grossly wrong readings.

Per-class CT validation (new in v1.3)

The schema validator _validate_ct_model_per_class rejects invalid sensor_class: × ct_model: combinations at the esphome config stage, before flash + boot. The allowed sets are not contiguous — this is explicit canon, not a bug:

sensor_class Allowed codes YAML names Behavior on mismatch
SCT_013 {1, 2, 3, 4, 6} SCT_013_005/010/030/050/020 cv.Invalid with a hint
WIRED_CT {1, 2, 3} WIRED_CT_1 / WIRED_CT_2 / WIRED_CT_3 cv.Invalid
BUILTIN_CT {} (none) cv.Invalid (any ct_model is rejected)
UNSET {} cv.Invalid (class not set)

Specifically:

  • SCT_013 non-contiguous: code 5 (SCT_013_100) and code 7 (60 A) are not allowed — the firmware does not load a factory coefficient table for them.
  • WIRED_CT is a roadmap SKU; on the current board it accepts codes 1/2/3 as factory preset slots (for future characterization). It does not activate on the SCT_013 board.
  • BUILTIN_CT is the onboard CT (built-in shunt); ct_model: is neither needed nor accepted. Declaring BUILTIN_CT without the matching hardware is pointless.

If the YAML slips past the validator (old schema + new firmware, manual override), the firmware returns REG_ERROR = 0xFE DEV_ERR_PARAM — the module will not write an unsupported code. Validated on the bench: an attempt to write code 5 (SCT_013_100) on v1.3 firmware → DEV_ERR_PARAM, the mirrors stay at the prior value.


How to Tell the Module

There are two keys in YAML — you pick one of the two depending on whether you have the same clamp on all channels or different ones. The syntactic transition is from a scalar value to a YAML list (array):

Step 1 — one clamp for all channels (ct_model:, scalar)

If you have a UI1 (single current channel) or a UI3 with identical clamps on all three channels — one line:

yaml
rbamp:
  id: meter1
  ct_model: SCT_013_030      # ← scalar value, one model for all channels

This is the most common case. Most deployments start with a single clamp model and never move beyond this line.

Step 2 — different clamps on different channels (ct_models:, list)

If you have a UI2 / UI3 and want to put different clamps on the channels (for example, a small clamp on a standby line, a large one on the mains feed) — replace ct_model: with ct_models: (with a trailing s) and use a YAML list in square brackets:

yaml
rbamp:
  id: meter_ui3
  ct_models: [SCT_013_005, SCT_013_030, SCT_013_020]
  #         ↑                            ↑                           ↑
  #     channel 0                     channel 1                channel 2
  #
  # This is a standard YAML list (1..3 elements).
  # Order matters: the position in the list = the channel index.
  # Validated v1.3 on the bench: codes [1, 3, 6] → mirrors `01 03 06`, no clobber.

This is the spot where people most often trip up when modifying multi-channel systems. Remember: ct_model: (no s) is a scalar value for a single model; ct_models: (with s) is a list of values in square brackets, one per channel. The list length must match the number of active channels on the module (1 for UI1, 2 for UI2, 3 for UI3).

Mutually exclusive. Declaring both ct_model: AND ct_models: at the same time is a schema validation error (cv.Invalid). Use only one of the two.

A UI3 Installation with Different Clamp Sizes

The canonical scenario for a home with its own generation or with mixed load types:

  • Channel 0 — small consumers (LED lighting, standby mode, electronics). An SCT_013_005 clamp (5 A) gives maximum resolution at low current.
  • Channel 1 — main loads (hob, water heater). An SCT_013_030 clamp (30 A) covers the typical household peak.
  • Channel 2 — a medium-power branch (water heater, ~3-5 kW). An SCT_013_020 clamp (20 A) is the sweet spot between accuracy and headroom for a typical submeter.

In a single rbamp: YAML block it is enough to declare:

yaml
rbamp:
  id: home_meter
  ct_models: [SCT_013_005, SCT_013_030, SCT_013_020]
sensor:
  - platform: rbamp
    rbamp_id: home_meter
    voltage:
      name: "Mains Voltage"
    current:
      name: "Lighting Current"     # SCT_013_005, channel 0
    current_1:
      name: "Appliances Current"   # SCT_013_030, channel 1
    current_2:
      name: "Boiler Current"       # SCT_013_020, channel 2
    # ...power_0/_1/_2, energy_0/_1/_2 likewise

The component itself assigns the exact model to each channel on boot.

What the Key Does Under the Hood

On firmware v1.2+, writing ct_model: / ct_models: atomically loads the factory coefficients (noise floor + gain) for the chosen model into the module's RAM and saves them to flash. No additional calibration steps are required on the user's side — the module ships from the factory with all the necessary coefficient tables.

On earlier firmware the value is stored as a model marker. Full auto-loading of coefficients will come with a firmware upgrade — the YAML will not need to change.

Read-compare-write (v1.3+) — why boot is now "instant"

On boot, the v1.3 component reads the current REG_CT_MODEL_CH0/1/2 (mirrors 0x51-0x53) and compares them with the YAML-requested values. If they match, the flash write is skipped entirely.

Boot scenario v0.4.0 (always-write) v1.3 (read-compare-write)
Config already applied (mirrors match) ~700 ms × N channels flash erase 0 ms (I²C read-back only)
Config changed (one model) ~700 ms ~700 ms (delta only)
UI3 with three different models (cold install) ~2.8 s blackout ~2.1 s (3 × 700 ms + verify)
UI3 with the same models (warm boot) ~2.8 s blackout every time ~0 ms

In practice: keep ct_model: / ct_models: in YAML forever — the config is idempotent and will not wear out the flash on repeat boots.

Canon order — descending iteration on multi-channel

On a cold install of three models the component iterates the channels in descending order (ch2 → ch1 → ch0) with a per-iteration sequence: REG_CT_MODEL=code → CMD_SET_CT_MODEL_CHn → CMD_SAVE_USER_CONFIG. This is canon A1 (order-independent CT bind) — validated on the bench in v1.3: mixed codes [1, 3, 6] on I3 → mirrors 01 03 06, no clobber.

The component itself feeds the watchdog (App.feed_wdt()) during each flash-write window — the typical ESPHome setup() budget of 15 s is not exceeded even on a UI3 cold install.


Verifying the Installation

After the first boot, check the readings on a purely resistive load — an incandescent bulb, a kettle, a heating element. A resistive load gives a known signal shape:

  • The power factor (power_factor) should be close to 1.00 (steadily > 0.95).
  • The active power (power) should be positive and stable.
  • The RMS current (current) should match P / U with reasonable accuracy.

If the readings do not add up: - current steadily ~0 with the load running → check the polarity and that the clamp encircles a single conductor (see below) - power consistently negative → flip the clamp on the conductor (arrow the other way) - power_factor ~0.5..0.7 on an incandescent bulb → there may be a reactive load nearby or the clamp may be installed incorrectly

Detailed symptom-oriented diagnostics are in 10_troubleshooting.md.


CT Clamp Polarity

The clamp body carries an arrow showing the direction of "normal" energy flow (consumption, toward the load). With correct installation (the arrow pointing in the direction of current into the load):

  • P_real > 0 — consumption.
  • P_real < 0 — export (STANDARD / PRO only).

If active power is negative with a consumer running — physically flip the clamp on the conductor. Do not correct polarity in software: it masks directional bugs in downstream automations.

The clamp must close completely around a single conductor. Do not pass both L and N through one clamp — their magnetic fields cancel out, and the sensor will read near zero.


Voltage Channel

UI* SKUs contain a built-in voltage transformer. The primary winding connects to mains L and N through the module's terminal blocks, and the secondary is loaded onto the board's burden network and connected to the ADC.

The transformer's factory configuration is fixed on the board revision — the user has nothing to configure. The voltage sensor is ready to work out of the box.

I-only SKUs (I1 / I2 / I3) have no voltage channel. The voltage slot returns 0 on them and must not be declared together with power: or energy: (the schema validator checks this dependency).


Multi-Channel Modules

On UI2 / UI3 each channel is a separate ADC + burden-network circuit, not a shared magnetic core. This allows you to:

  • Put a single CT model on all channels (ct_model:) — the typical configuration for uniform loads.
  • Put different models on different channels (ct_models:) — to optimize accuracy on mixed installations (see above).
  • Dedicate one channel to consumption and another to solar export — the polarity on each channel is set independently by the physical direction of the clamp.