Identity and discovery

How a host recognises an STD module, what it is, and what it can do. All registers in this chapter are read-only unless stated otherwise. I²C addresses; Modbus discovery mirrors are listed at the end.


Discovery sequence

On first contact a master reads the identity block at 0x0000 and gates everything else on it:

  1. ID (0x0000, 2 bytes) must read 'S','T' (0x53, 0x54) — anything else is not an STD module.
  2. VERSION (0x0003) is the register-map layout version (current: 0x36). Feature additions bump it; a master gates map features on it.
  3. CAPABILITIES (0x0004, u16) — feature bitmap, see below. Bit 9 (16-bit addressing) is always set on STD.
  4. N_VOLTAGE (0x0007) / N_CURRENT (0x0008) — how many channels are populated. Channel blocks at index ≥ N are reserved; their value is unspecified.
  5. VARIANT (0x0009) — family member code.
  6. UID (0x00F4, 12 bytes) — the chip's unique id. Addresses can be changed; the UID cannot: use it as the device identity in any database.
  7. FW_VER (0x0114, u32) — the running firmware version (use it for inventory and update decisions). Read it as major.minor = the high word and the low word in decimal: 0x0001007E is shown as STD firmware 1.126. The register-map version (VERSION, 0x0003) is separate.

Identity registers

Addr Name Type Meaning
0x0000 ID 2×u8 'S','T'
0x0002 ERROR u8 result of the last command (see Commands)
0x0003 VERSION u8 register-map version (0x36)
0x0004 CAPABILITIES u16 feature bitmap
0x0006 STATUS u8 live status bits (see Diagnostics)
0x0007 N_VOLTAGE u8 voltage channels, 0..8
0x0008 N_CURRENT u8 current channels, 1..64
0x0009 VARIANT u8 family member code
0x000A HW_REV u8 hardware revision
0x000B FW_VERSION u16 firmware line marker — not the image version
0x00F4 UID 12×u8 unique chip id
0x0114 FW_VER u32 running firmware version: high word . low word, decimal (0x0001007E = 1.126)
0x017C BOARD_ID u32 board id of the running image (see below)

⚠ Two "firmware version" registers exist for historical reasons. FW_VERSION (0x000B, u16) only marks the firmware line. The actual, monotonically increasing firmware version is FW_VER (0x0114, u32), shown as major.minor — use it for inventory and update decisions.

BOARD_ID (0x017C)

BOARD_ID identifies the board the running image was built for: ("BD" << 16) | channel-count << 8 | VARIANT = 0x4244nnvv — e.g. 0x42440211 for STD-UI1. Every release image carries the same word, covered by the image's integrity and signature checks; a firmware update with a different board id is refused (see Firmware update). Compare BOARD_ID with the release file before sending an update.


CAPABILITIES bitmap (0x0004)

Bit Name Meaning
0 SIGNED signed power/energy (import/export)
1 REACTIVE Q and S published
2 THD THD / displacement-PF fields live (0 → those fields read 0 on I²C, the sentinel on Modbus native)
3 HARMONICS per-harmonic spectra (industrial tier)
4 INDUSTRIAL industrial tier build
5 HUB_IFACE hub-side interface
6 OTA firmware update over the bus
7 ENERGY per-window energy accumulators
8 MULTI_LATCH eight snapshot banks present — see Snapshot banks
9 ADDR16 16-bit register addressing (always 1 on STD)
10 MULTI_CHANNEL more than one current channel
11 MODBUS_IFACE Modbus RTU transport present
12 RTC battery-backed on-device clock (0 — time comes from the master)
13 ONDEVICE_ENERGY cumulative energy counters persisted on the device
14 CHMAP_PERSIST per-channel CT-model map persists (reserved; 0 until implemented)
15 ENERGY_UWH µWh-resolution energy counters published (active µWh and reactive µvarh) — see Measurement & energy

A master treats unknown bits as "feature absent" and never relies on reserved fields.

Honest-capabilities rule: a module reports only what the running build actually provides. For example, the three-phase firmware reports THD = 0 and RTC = 0 (the master feeds the clock); modules modules without snapshot banks report MULTI_LATCH = 0 (energy is read from cumulative counters).


VARIANT codes (0x0009)

Code Member Channels
0x11 STD-UI1 1 V + 1 I
0x63 STD-U3I3 3 V + 3 I (three-phase)

Other codes in the enum space are reserved and must not be assumed absent-forever; a master decides by N_VOLTAGE / N_CURRENT + CAPABILITIES, not by hardcoding variant codes.


Modbus discovery mirror

The same identity set is readable over Modbus as input registers at 0x6000: MAGIC 0x6000 · MAP_VERSION 0x6001 · FW_VERSION 0x6002 · HW_REV 0x6003 · CAPABILITIES 0x6004 · N_VOLTAGE 0x6005 · N_CURRENT 0x6006 · VARIANT 0x6007 · TIER 0x6008 · STATUS 0x6009 · ERROR 0x600A · UID 0x600B–0x6010 (12 bytes, big-endian by register) · FRAME_CNT 0x6011–12 · FREQ 0x6013 · WINDOW_MS 0x6014 · CMD_SEQ 0x6015 · RING_DROP 0x6016 · WIN_NSAMP 0x6017 · WIN_PERIOD 0x6018 · CPU diag 0x6019–0x601C · LOST_FRAMES 0x601D–1E · WIN_SEQ 0x601F. BOARD_ID is holding 0x831B–1C; FW_VER is holding 0x8315–16.