Measurement and energy model

What the numbers in the map mean, when they update, and how energy is kept so that a power cut, reset or firmware update never silently loses or invents it.


Sampling and windows

  • All channels are measured synchronously; power is computed from every measurement point (u·i).
  • Samples aggregate into measurement windows of whole mains cycles nearest 100 ms — 5 cycles at 50 Hz, 6 at 60 Hz (a fixed-length fallback without mains lock). Each finalized window is published atomically as a complete snapshot (all channels + totals); WIN_SEQ steps and DRDY pulses once per window, i.e. about 10 times a second. Without mains lock the module keeps publishing on a slower fixed fallback tick, so WIN_SEQ and DRDY never stop (DRDY).
  • Polling faster than the publish rate returns the same data. WIN_NSAMP (samples in the last window) and WIN_PERIOD (measured mains period in samples) describe the current lock.
  • Mains frequency (FREQ, cHz) is derived from zero crossings over wall time (~2 s update) and is immune to sample drops; outside the measurable band it reads 0. STATUS bit 2 (mains_ok) is set while channel-0 voltage is above ~50 V — it is a mains-present flag, not a frequency check.
  • Lost samples are compensated: if an internal operation (e.g. a firmware-update flash write) costs measurement frames, the gap is counted (LOST_FRAMES) and the energy integral is compensated in the energy counters.
  • Low currents: below roughly 20 mA the published current value is additionally smoothed over a few seconds for a stable reading (power and energy are unaffected); the smoothing resets on a load step, so transitions stay fast.

Published quantities

Per voltage channel: RMS voltage. Per current channel: RMS current, active power (signed), reactive power (signed), apparent power, power factor (signed). Per device: frequency, totals. Units and scales — see Conventions.

  • Signs: P > 0 import; PF carries the sign of P; Q > 0 inductive (IEC 62053-23).
  • TOTALS k = 0 is the grand total over all channels; k = 1..3 are per-phase totals (phase = channel on three-phase members; single-voltage builds sum everything into k = 1). TOTALS carry I/P/Q/S/PF only — their energy field positions read 0. Grand import is the positive part of the aggregate power per window — the net at a service entry — which differs from the sum of per-channel imports when phases disagree in direction; both views are available.
  • Voltage phase angle: each voltage channel publishes the fundamental's phase angle relative to voltage 0 (ANGLE, 0.01°, range (−180°, +180°]). Voltage 0 reads 0 by definition; 0x8000 means no angle (that input, or voltage 0, is below 50 V). On a forward sequence v1 ≈ −120°, v2 ≈ +120°.
  • Phase sequence (PHASE_SEQ 0x0012), derived from the voltage angles: 0 = not available (fewer than 3 voltage inputs, or one below 50 V) · 1 = forward L1-L2-L3 · 2 = reverse · 3 = abnormal (no 120° pattern — e.g. two inputs wired to the same phase). A useful installation check before trusting per-phase readings.

Energy

Per-window accumulators (realtime block)

E_POS / E_NEG in each current channel integrate signed energy in mW·samples since boot (TOTALS do not carry them). The split is per window: each window's energy lands in the import or export bucket by the sign of that window's power, so a mixed flow splits correctly. These are diagnostic/derivation values — use the cumulative counters for totals.

Cumulative counters

The ENERGY block (0x0800) holds life-time, device-persisted cumulative energy: active import/export/net in whole Wh and in mWh (i64), reactive import/export in varh. Modules with capability bit 15 also publish the active counters at µWh resolution — grand import/export/net at 0x08D0/0x08D8/0x08E0 and per channel at 0x0C80 + g·0x10 — in the same snapshot as the mWh fields. Import/export mWh = floor(µWh / 1000); the net counter, in mWh and in µWh alike, is import − export in that unit (with a negative net its mWh value can differ from floor(net µWh / 1000) by 1). Rules:

  • Read energy from the module; never integrate P·dt on the host. The module's sample-domain integral is gap-compensated and survives restarts; a host-side integral is neither.
  • Interval energy = delta of two cumulative readings at the interval boundaries. The counters are monotonic within a generation; a missed boundary merges two intervals and loses nothing.
  • Persistence: after a restart the counters continue from the last saved value — they never go below it; energy during the restart itself is not measured. The grand counters are saved every second including the sub-Wh remainder, and mirrored every publish window (~100 ms) to a backup area that survives a warm restart (reset, watchdog, firmware update). So: a warm restart resumes from about the last window; an ungraceful power loss loses at most about the last second of energy (P × 1 s — e.g. ~3 mWh at 10 kW). The per-channel counters are saved every second as whole mWh, so their step-back adds less than 1 mWh on top. After a restart a counter may therefore resume slightly below the last value read — take the delta as max(0, new − last) and re-anchor; do not discard the period.
  • µWh counters: the same counters, the same rules — the restart step-back above applies unchanged (grand: about a second of energy; per-channel: plus the unsaved sub-mWh remainder). Take max(0, Δ) exactly as for the mWh fields.
  • µvarh counters (same capability bit 15): reactive import/export at µvarh resolution, 0x08E8/0x08F0 — grand only (there is no per-channel reactive energy); varh = floor(µvarh / 1 000 000); same snapshot and restart rules as the µWh fields. The coherent fine-resolution read is one transaction over 0x08D0–0x08F7 (40 B): active µWh import/export/net + reactive µvarh import/export.
  • Starting current (CFG_START_UA 0x0084): while a channel's current is below this threshold, that channel adds no active or reactive energy to any counter — grand or per channel. Readings (I/P/Q/S/PF) are not affected. This stops the no-load creep where measurement noise of either sign would slowly feed both import and export; loads above the threshold are counted fully, starting within about a second of switch-on. Default 400 µA; 0 disables it; 10 µA steps up to 2540 µA (out-of-range writes are rejected). A write applies at once; SAVE_CONFIG persists it.
  • Generations: LT_GEN (0x0840) increments on every counter reset or adopt. Never take a delta across a generation change — re-anchor instead. Resets/adopts are keyed commands and are event-logged with before/after values (Commands).
  • Per-channel counters (GROUP_ENERGY, group g = channel g) are persisted every second too but are informative: they restart at 0 with a generation change or on new/foreign storage (LTG_STATUS = 3, transient — clears after the first per-channel write, ~1 s). The grand block is the cumulative counters.
  • Store health: LTA_STATUS ≠ 0/1 (FAULT/CORRUPT) means energy is not persisting — the device keeps metering and recovers by itself when the store returns; STATUS bit 5 mirrors it. Records in the store are authenticated; foreign or edited records are rejected and counted (NVM_REJ_CNT). (Rollback-anchor detection — SEC_ROLLBACK, events 10/11 — is reserved.)

Snapshot banks (capability bit 8)

When CAPABILITIES bit 8 = 1 the module keeps eight independent snapshot banks (master-timed period snapshots with per-channel energy). Use them when several modules must cut the same period at the same instant; for a single module, cumulative-counter deltas (above) are the simpler way. Gate usage on the capability bit.

  1. Arm. Write PERIOD_ARM (0x0063): bit b = 1 makes bank b accumulate window by window. A newly armed bank starts empty. The first 3 windows after a boot are not accumulated: a bank snapshotted during them holds zeros with WIN_CNT = 0 and its PD_VALID bit set. Banks are not kept across a reset (PD_VALID = 0 after it).
  2. Snapshot. Write LATCH_BANK (0x0062) = b, then command 0x03 (LATCH_PERIOD). The cut is made at the next window boundary; the bank's P/Q/S are the average over the windows since it was armed or last snapshotted, and the bank restarts from zero. On a Modbus bus the same writes may be sent on broadcast (unit 0) for a synchronized cut across modules.
  3. Wait. CMD_SEQ steps when the command is accepted, before the cut. After it steps, wait until WIN_SEQ (0x0016) has advanced by 2 (about 200 ms) and then read the bank.
  4. Read. The snapshot is read directly from the bank (layout); PD_VALID bit b tells that the bank holds a snapshot (it stays set — it is not a freshness flag). A bank is updated only when a snapshot is taken.

Time

Modules have no battery clock (capability bit 12 = 0). The master owns time:

  • After every module reset the clock is invalid: STATUS bit 4 (time_valid) = 0, RTC_EPOCH reads 0. The master writes the epoch to TIME_SET (0x08C0; Modbus 0x8100–01) and issues command 0x06 — at discovery and whenever it sees time_valid = 0.
  • Cumulative energy does not depend on the clock. Only timestamped history pauses until time is set.
  • Before the first time-set nothing is bucketed into history. The first set opens a period flagged PARTIAL + POWERUP; a later step/correction marks the affected period with the CLOCK flag. Time never moves backwards inside the history.

History records

The module keeps the last 7 hourly records in non-volatile memory (a deeper archive belongs to the master). Query interface: register map.

  • Last finished 15-minute summary — electrical values only, from RAM (lost on reset; HIST_CAP reads 0 here).
  • Hourly ring — persisted, the last 7 records; read the count from HIST_CAP (0x0C08).
  • Records are written only while the clock is valid.

Record layout (80 B, little-endian):

Off Field Type Meaning
0x00 TS u32 period start, unix
0x04 FLAGS u16 see below
0x06 N u16 15-min: 200-ms snapshots in the period · hourly: 15-min children (4 = complete)
0x08 V_DV u16 average voltage (channel 0), 0.1 V
0x0A I_MA u32 average current (sum of channels), mA
0x0E / 0x12 / 0x16 P_W / Q_VAR / S_VA i32 each period averages, W/var/VA
0x1A PF i16 Q10
0x1C–0x2B MIN_P / MAX_P (i32, W) · MIN_I / MAX_I (u32, mA) period envelope
0x2C / 0x32 E_IMP_WH / E_EXP_WH u48 absolute life-time Wh at period end
0x38 / 0x44 PH_IMP_CWH / PH_EXP_CWH u32×3 per-phase period energy, 0.01 Wh

Flags: bit0 PARTIAL (period not fully observed) · bit1 POWERUP (first after a boot) · bit2 CLOCK (time set/stepped inside the period) · bit3 LTA_JUMP (life-time reset/adopt inside the period). Diff consecutive records only when the timestamp steps by exactly one period and neither record has LTA_JUMP — the absolute Wh fields make gap-filling after a master outage exact.


Event log

HIST_PERIOD = 2 selects the event log ring through the same query window. Every metering-relevant action leaves a 32-B record with before/after values:

Off Field Type
0x00 TS u32 (0 = clock was not set)
0x04 UPTIME_S u32
0x08 TYPE u8
0x09 FLAGS u8
0x0A BOOT u16 (boot counter)
0x0C / 0x10 A_BEFORE / A_AFTER u32 (meaning per type)
0x14 / 0x1A E_BEFORE / E_AFTER u48, grand import Wh

Event types: 1 counter reset · 2 counter adopt · 3 late counter load (store recovered from FAULT) · 4 legacy-store migration · 5 calibration save (A = calibration checksum) · 6 firmware commit (A = version before → after) · 7 history clear · 8 late config load · 9 foreign store records rejected (A = count / first address) · 10/11 reserved.

Capacity on current boards: 10 event records (HIST_CAP with HIST_PERIOD = 2).


Boot readiness

Right after a boot a host should expect: the register interface answers, but measurements and WIN_SEQ read 0 until the first publish (about one window after start — ~100 ms); the first ~3 windows add no energy (settling); FREQ reads 0 for the first ~2 s; the certificate check runs ~3 s after boot (SEC_CERT_STATE = 3 until then). Allow ~1 s before judging health.