Troubleshooting

This chapter is a quick reference for common problems and their solutions. Each entry follows the structure:

  • Symptom — what the user observes
  • Causes — why it can happen
  • What to check / do — concrete actions

I²C bus

1. NACK / no response from the module

Symptom: Wire.endTransmission() returns non-zero; i2cdetect does not show the address on Linux; rb_read_u8() returns 0xFF.

Causes and checks:

  • Module power is missing or unstable — measure VCC with a multimeter; it must be 5 V ±5%.
  • No common ground — the single most frequent mistake. Master GND and module GND must be tied together.
  • SDA and SCL swapped — verify against the wiring diagram in Hardware connection.
  • No pull-ups on the bus — if the built-in pull-ups have been cut on a module and no external ones are installed, the bus is dead. With everything unpowered, measure SDA↔VCC: it must read 1.5–4.7 kΩ.
  • Too many pull-ups in parallel — built-in pull-ups still active on every module, plus master pull-ups, dropping the equivalent below ~1 kΩ. The master cannot pull the bus to LOW. Cut the built-in pull-ups on all but one module.
  • Long cable without twisted pair or buffer — past ~0.3 m, parallel wires couple capacitively and edges round off. Use UTP cat-5 (up to 1 m) or a PCA9515 buffer (up to 3 m). See Hardware connection — Bus length.
  • Wrong slave address — the module may have been readdressed. Run an I²C scan:
cpp
void i2c_scan() {
  for (uint8_t addr = 0x08; addr < 0x78; addr++) {
    Wire.beginTransmission(addr);
    if (Wire.endTransmission() == 0) {
      Serial.printf("Found device at 0x%02X\n", addr);
    }
  }
}
  • I²C speed too high for the cable length. Drop to 50 kHz: Wire.setClock(50000);.

2. Burst read returns the same byte four times (auto-increment trap)

Symptom: a 4-byte burst read of 0x86 (intended to read U_rms as float32) returns four identical bytes — or all zeros, or all 0xFF. Voltage readings look plausible-shaped but completely wrong (e.g. 127.0 always, regardless of mains).

Cause: rbAmp does not auto-increment its internal register pointer. Code that issues a single Wire.requestFrom(addr, 4) after Wire.write(0x86) reads the byte at 0x86 four times, not bytes 0x86, 0x87, 0x88, 0x89. This is the most reflexive coding mistake for engineers used to PZEM / ATM90E32 / 24Cxx EEPROMs where multi-byte burst reads are standard.

Solution: read each byte with its own transaction and explicit register address. Use the rb_read_float_le() helper in Initialization — it loops rb_read_u8(addr, reg + i) for i = 0..3. Same for u32 reads (see Period metering — Clock-drift diagnostics).

3. Intermittent read/write timeouts

Symptom: transactions succeed sometimes, fail other times — especially in electrically noisy environments or near inductive loads.

Causes:

  • ❌ Long cable without twisted pair
  • ❌ Cable routed parallel to mains wiring → 50 Hz / 100 Hz coupling
  • ❌ Noisy ground on the master side (e.g. a separate regulator without bulk capacitance)
  • ❌ Stray capacitance between SDA and GND > 100 pF (e.g. a splice with long stubs)

Solutions:

  • Use twisted pair (SDA + GND in one pair, SCL + GND in the other)
  • Avoid routing I²C parallel to power wiring in the same conduit
  • Reduce speed to 50 kHz / add 100 nF between VCC and GND of the module near the connector
  • For long runs outside an enclosure, add ESD protection (TVS diodes on SDA and SCL)

4. DATA_VALID (0xCE) never becomes 1

Symptom: master reads 0xCE and always gets 0x00. Other registers may also stay at zero.

Causes:

  • ❌ The module has not finished booting (normal for the first ~250 ms after power-on)
  • ❌ Firmware initialisation error — read REG_ERROR (0x02):
  • 0xFB (ERR_FLASH_PARAMS_BAD) — flash parameter block is corrupted; the module runs on defaults. Recalibrate / reprovision.
  • 0xFA (ERR_LUT_BAD) — ADC LUT calibration is broken. Not fatal — measurements still work, but accuracy is slightly degraded.
  • ❌ MCU clock failure (rare) — power-cycle the module

Solutions:

  • Wait 300 ms after power-on before polling 0xCE.
  • If DATA_VALID = 1 is not seen after > 1 s — power-cycle.
  • If the problem persists after a power-cycle — check power (ripple, brown-out).

Calibration and accuracy

5. I_rms close to 0 while a load is running

Symptom: the lamp is lit, the heater is warm, but I_rms shows 0.001 A or jitters between 0 and a few mA.

Causes (in decreasing order of frequency):

  • CT clamp not on the wire — the conductor goes past the clamp instead of through it.
  • CT clamp on both L and N at the same time — fluxes from line and neutral cancel, the sensor reads near zero. See Hardware connection — Current sensor. The clamp must be on one conductor (line/L).
  • Clamp not fully closed — a gap > 0.1 mm between the core halves dramatically increases magnetic reluctance, so the sensor output drops well below normal. Unclip and re-clip until it clicks shut. Dirt or oxide in the gap is a common culprit — wipe the mating surfaces.
  • Loose 3.5 mm jack — remove and reinsert the plug.
  • REG_CT_MODEL not set — the module does not know the sensor's sensitivity. See Initialization — Setting the external sensor model. Register 0x05 must contain the correct model code.
  • Wrong model code written — for example, an SCT-013-030 sensor with the SCT-013-100 code → current shown will be 3.3× lower than reality. Verify the sensor's case marking against the model code.
  • Current below the noise floor — for very small loads (< ~10 mA on a 30 A clamp) the sensor output is close to ADC noise. The firmware applies quadrature noise subtraction: I_corrected = √(I_raw² − NF²). If I_raw ≤ NF, the result is clamped to 0. This is intended behaviour.

6. I_rms off by a large factor

Symptom: real load is ~10 A (per reference meter), the module shows 3 A or 30 A.

Causes:

  • Wrong CT model code — most common case. See #5.
  • Wrong CT model installed — somebody fitted a 100 A clamp where the configuration calls for a 30 A clamp (or vice versa).
  • Clamp not fully closed (see #5) — typically reads 5–20 % low.
  • Factory calibration disturbed (I0_GAIN at 0xF4..0xF7 has an abnormal value). Check:
cpp
float gain = rb_read_float_le(0x50, 0xF4);
Serial.printf("I0_GAIN = %.4f\n", gain);

Normal range: 0.9…1.1. If far outside, the module needs service / factory recalibration.

7. Sign of P_real is wrong (consumption shows as export)

Symptom: the load is clearly consuming (warm heater, lit lamp), but P_real < 0.

Causes and solutions:

  • L and N swapped on the voltage terminals — the most common cause. See Hardware connection — Voltage sensor. Swap L and N on the PCB.
  • CT clamp installed backwards — the arrow on the clamp must point in the direction of current toward the load (panel → load). If it points the other way, unclip and reverse the clamp.
  • Physical reversal is impractical — compensate in master code:
cpp
float p_corrected = -p_raw;

but the physical fix is preferable — otherwise every piece of code must remember the inversion.

8. Energy total disagrees with a reference meter by a few percent

Symptom: E_Wh over one hour differs from the utility meter by 2–10 %.

Likely causes (in decreasing order):

  • Clamp not fully closed (gap) — typically −5 to −20 % low. The single most common cause. Unclip, clean the mating surfaces, clip again until fully shut.
  • Clamp installed on a "secondary" wire — inside the breaker panel, on a short pigtail past a breaker. Stray fields from neighbouring breakers introduce errors. Move the clamp onto the main feed or onto an isolated section of conductor.
  • Close to strong reactive loads — near transformers, asynchronous motors, UPSes. Magnetic fields from neighbouring inductors create a stray signal. Move the clamp ≥ 10 cm away from any ferromagnetic component.
  • Low PF (≤ 0.5) — large reactive loads require precise phase compensation. Factory calibration assumes cos(φ) = 1.0 (resistive loads) with a ~5-sample compensating shift. For specific cases tune REG_V03_PHASE_SAMPLES (0x06).
  • Distorted mains voltage (micro-sags, high-order harmonics) — RMS and mean computation are more robust than peak detection, but distortions can still introduce 1–3 % error.
  • Damaged CT cable or loose jack — open-circuit or cold-solder inside the plug. Check with a multimeter (the CT clamp is a step-down transformer; the secondary winding should read 50–200 Ω depending on model).

9. avg_P_W is much lower than expected

Symptom: a 1000 W heater is on, RT P_real ≈ 1000 W, but PERIOD_AVG_P_W reads ~200 W over a one-minute period.

Causes:

  • ❌ The load is actually intermittent (cycling thermostat, pulsing element) — avg_P_W correctly reports the time average. Cross-check with PERIOD_MAX_P_W (0xE0) to see the peak inside any 200 ms window.
  • ❌ If the load is steady and RT P_real ≈ avg_P_W does not hold:
  • On BASIC tier: check the RT sign of P_real. If P is occasionally negative (a solar inverter is feeding back, for example), negative samples are excluded from PERIOD_AVG_P_W, dragging the average down. See Period metering — BASIC tier.
  • On STANDARD / PRO: compute total_avg = avg_P_consume + avg_P_export (export taken as magnitude) to see the channel's true activity.

10. PERIOD_VALID = 0 after a latch

Symptom: the master issues CMD_LATCH_PERIOD, reads 0x07, gets 0. Snapshot is not fresh.

Causes:

  • Latches too close together — no RT window (200 ms) completed between two latches. The accumulator is empty, the snapshot is discarded.
  • Race with an RT commit — rare: the master wrote the command at the exact instant the firmware was committing the live accumulator. Possible on very fast masters.

Solution — the retry pattern (see Period metering — Basic cycle):

cpp
if ((rb_read_u8(0x50, 0x07) & 0x01) == 0) {
  delay(250);   // let at least one RT window complete
  rb_write_u8(0x50, 0x01, 0x27);
  delay(50);
  // retry read of PERIOD_VALID
}

Multi-module issues

11. Address collision

Symptom: several modules added to the bus — some "vanish" or return garbage. The same address answers with different values.

Cause: two or more modules share the same address → I²C arbitration / collision. Frequent right after unboxing, when every module is on the factory default 0x50.

Solution:

  1. Disconnect every module.
  2. Reconnect one at a time; readdress each to a unique address.
  3. After readdressing all modules, reconnect them in parallel.

See Initialization — Recommended workflow.

12. Wired-OR DRDY fires several times in quick succession

Symptom: with wired-OR DRDY, the master EXTI fires every 1–5 ms a few times in a row.

Cause: the modules are not perfectly synchronised — each has its own crystal, and RT window periods differ slightly (199.8 ms vs 200.1 ms). Over the ~200 ms span, the modules pull the line at slightly different instants.

This is normal. Solutions:

  • Ignore "double" triggers: after the first trigger, read all modules; suppress further triggers within ~10 ms.
  • Use broadcast latch (see Period metering — Approach 2) for precise synchronisation — but only for period snapshots, not for RT.
  • Move to DRDY-per-module — each module on its own GPIO.

13. I²C bus busy when DRDY fires

Symptom: DRDY fires while the master is already in a transaction with another module. The EXTI handler is delayed.

This is normal. The RT registers remain valid until the next commit (200 ms later). The master:

  • Finishes the current transaction.
  • Services the delayed EXTI and reads the next module.
  • Latency: 1–10 ms typically — not critical.

14. Multi-module clock drift in long tests

Symptom: cumulative energy diverges between modules by fractions of a percent over a week.

Cause: each rbAmp has its own crystal with ±50 ppm drift (1–5 s/day).

Solution — built into the architecture: the master uses its own clock to multiply by dt. All modules share the same time reference, so the system-wide Wh total does not diverge.

To measure chip drift for QA, compare PERIOD_LATCH_MS (0xEC) with master dt. Note rbAmp has no pointer auto-increment, so a u32 read requires 4 separate transactions (see helper in Period metering — Clock-drift diagnostics):

cpp
uint32_t chip_dt = rb_read_u32_le(0x50, 0xEC);
float ratio = (float)chip_dt / (float)master_dt;
printf("Chip drift: %.3f (1.000 = perfect)\n", ratio);

Acceptable range: 0.97–1.03 (3 % drift = 4 min/day — large, but harmless for energy). Beyond this range, the module needs service.


Power and flash

15. Power loss during CMD_SAVE_GAINS → partial flash write

Symptom: after a power interruption during SAVE_GAINS, the module boots with REG_ERROR = 0xFB (ERR_FLASH_PARAMS_BAD).

What happened: the firmware detected a CRC failure in the flash parameter block, loaded defaults, and rewrote them.

Solution:

  • Factory defaults are restored — the module works, but with baseline accuracy.
  • If you had configured a custom address or CT model, write them again and issue SAVE_GAINS.
  • To avoid this in the future: do not cut power immediately after SAVE_GAINS — wait at least 1 second.

16. Module is hot

Symptom: the enclosure feels noticeably warm.

Normal: at mains current up to nominal (SKU-dependent), light warming of the LV side (LDO regulator) up to ~40 °C is expected.

Not normal: hot enclosure (≥ 60 °C), burning smell, plastic discoloration.

Causes:

  • ❌ Overvoltage on the LV side (VCC > 5.5 V) — check the supply.
  • ❌ Internal damage on the mains side (short in the divider or CT circuit).
  • ❌ External CT overloaded (current beyond the sensor range).

Action: disconnect power immediately, isolate the module, contact the supplier.


Sensor wiring — critical errors

17. Sanity check — what "correctly wired" means

After installing or reinstalling a module, run a smoke test with a known purely-resistive load (incandescent bulb, electric kettle, heating element) — for example, a 100 W bulb on 230 V.

Expected:

  • U_rms ≈ 220..240 (depends on local mains)
  • I_rms ≈ 100 W / 230 V ≈ 0.43 A
  • P_real ≈ +100 W (positive, consumption)
  • PF ≈ 0.998..1.000 (resistive load)
  • Q ≈ 0 (no reactive content)

If P_real is negative: see #7 — L/N swapped or CT installed backwards. If |I_rms − expected| > 10 %: see #6 — wrong CT model or clamp not closed. If |P_real − U × I| > 5 % at PF = 1: phase compensation may be off — contact the supplier.

18. Pre-commissioning checklist

Before powering up a module in a production system:

  • L wired to the L terminal of the PCB (not swapped with N)
  • CT clamp on the **L conductor** (not on N, not on both at once)
  • Arrow on the CT clamp **pointing toward the load**
  • CT clamp fully closed (no gap, no slack — clip until it clicks)
  • CT cable intact, jack fully seated in the socket
  • Power VCC = 5 V ±5 %, clean ground
  • I²C pull-ups verified (see [Hardware connection — I²C pull-ups](/docs/modules-basic-standard-hardware-connection#ic-pull-ups--installed-on-the-board))
  • For modules with a plug-in CT: `REG_CT_MODEL` written and saved to match the installed sensor
  • Smoke test with a resistive load completed — all five values (U, I, P, PF, Q) within the expected ranges
  • If any item is unchecked, expect strange readings. The most common causes of metering errors are sensor installation issues, not firmware or electronics faults.


    Error codes (REG_ERROR = 0x02)

    Code Name Meaning Action
    0x00 ERR_OK Normal
    0xFA ERR_LUT_BAD ADC LUT calibration CRC failed; the module runs on linear approximation Not fatal. ADC accuracy may be off by 1–5 %. Have the supplier recalibrate.
    0xFB ERR_FLASH_PARAMS_BAD Flash parameter block corrupted; defaults restored Reconfigure address / CT model and SAVE_GAINS.
    0xFC ERR_NOT_READY First RT window has not yet completed after boot Wait 300 ms.
    0xFD ERR_SENSOR_OVERFLOW Signal clipping on the ADC rails (full-scale exceeded) Reduce current or use a larger CT.
    0xFE ERR_PARAM Invalid command code or out-of-range value Check command and value range.
    0xFF ERR_UNHANDLED HardFault or unhandled condition Power-cycle. If it recurs, contact the supplier.

    The register is read-only; it is cleared only on reset or power-cycle.


    When to contact the supplier

    Symptoms that warrant service:

    • The module does not exit DATA_VALID = 0 after three power-cycles
    • ERR_UNHANDLED (0xFF) recurs
    • I0_GAIN (0xF4) lies outside 0.9…1.1, or is unreadable
    • The enclosure is hot or smells of burnt material
    • Disagreement with a reference meter > 5 % despite the checklist in #18 being satisfied
    • A new module boots with ERR_LUT_BAD (0xFA) on first power-on

    See also